AHKC-EKB Split Core Current Sensor
Product Description
-
Detailed description
-
Parameters
-
Certificate
-
Download
-
- Small package size
- Low power consumption
- Extended measuring range
- Measurement:AC, DC, pulse and other complex current
▋ Product Overview
▋ Dimension
Bottom View Front View Side View ▋ Wiring Illustration
Clamp-on (Split-core) Installation on Measuring DC Cable Wiring of Auxiliary Power Supply Input&Transduced Signal Output ▋ Package&Shipment
Packaging Overview(Inner) Packing Dimension and Weight(Minimum) Minimum Package Contain 1 pcs ProductsDimension: 180mm*170mm*95mm Total N.W. (1 pcs)0.3 KG Packing Dimension and Weight(Large) Large Package Contain 60 pcs ProductsDimension: 455mm*455mm*200mm Total N.W. (60 pcs)19 KG AverageLead Time Manufacturing: 3~4 days
(If paired with system need extra 1~2 days for adjustment)Shippment: 8~9 days(World Wide Shipment) ProductHS Code 9030339000 COCountry of Origin China ▋ Series Overview
Image Model&Type Input Output Aperture AHKC-EKAOpen-loop Split-core Hall Effect Transducer 0~500A AC or 0~±500A DC 0~±5Vdc/±4Vdc φ20mm AHKC-EKAAOpen-loop Split-core Hall Effect Transducer 0~±500A DC 4~20mA DC φ20mm AHKC-EKBOpen-loop Split-core Hall Effect Transducer 0~1000A AC or 0~±1000A DC 0~±5Vdc/±4Vdc φ40mm AHKC-EKBAOpen-loop Split-core Hall Effect Transducer 0~±1000A DC 4~20mA DC φ40mm AHKC-EKCOpen-loop Split-core Hall Effect Transducer 0~1500A AC or 0~±1500A DC 0~±5Vdc/±4Vdc φ55mm AHKC-EKCAOpen-loop Split-core Hall Effect Transducer 0~±1500A DC 4~20mA DC φ55mm AHKC-BSOpen-loop Solid-core Hall Effect Transducer 0~500A AC or 0~±500A DC 0~±5Vdc/±4Vdc 20.5mm x 10.5mm AHKC-EOpen-loop Solid-core Hall Effect Transducer 0~500A AC or 0~±500A DC 0~±5Vdc/±4Vdc φ20mm AHKC-FOpen-loop Solid-core Hall Effect Transducer 0~1000A AC or 0~±1000A DC 0~±5Vdc/±4Vdc 43mm x 13mm AHBC-LTAClose-loop Solid-core Hall Effect Transducer 0~300A AC or 0~±300A DC 50mA/100mA φ20mm AHBC-LT1005Close-loop Solid-core Hall Effect Transducer 0~1000A AC or 0~±1000A DC 200mA / AHBC-LFClose-loop Solid-core Hall Effect Transducer 0~2000A AC or 0~±2000A DC 400mA / -
Size
Specification
Outline size
Through size
Mounting size
W
H
D
a
e
φ
M
N
AHKC-EKA
60
64
16
/
/
20
47
/
AHKC-EKAA
60
64
16
/
/
20
47
/
AHKC-EKDA
60
64
16
/
/
20
47
/
AHKC-EKB
100
102
24
/
/
40
80
/
AHKC-EKBA
100
102
24
/
/
40
80
/
AHKC-EKBDA
100
102
24
/
/
40
80
/
AHKC-EKC
115
110
27
/
/
55
95.5
/
AHKC-EKCA
115
110
27
/
/
55
95.5
/
AHKC-EKCDA
115
110
27
/
/
55
95.5
30
AHKC-K
127
63
25
64
16
/
/
30
AHKC-KAA
127
63
25
64
16
/
/
30
AHKC-KDA
127
63
25
64
16
/
/
46
AHKC-H
149
79
25
82
32
/
/
60
AHKC-KA
176
95.5
29
104
36
/
/
80
AHKC-HB
204
111.5
29
132
52
/
/
48*2
AHKC-HBAA
204
111.5
29
132
52
/
/
48x2
AHKC-HBDA
204
111.5
29
132
52
/
/
48x2
Model
Rated current
Power supply
Rated output
Measuring Aperture(mm)
Accuracy
AHKC-EKA
0~(20-500)A
±15V
5V/4V
φ20
1
AHKC-EKAA
DC 0~(50-500)A
12V/24V
4~20mA
φ20
1
AHKC-EKDA
AC 0~(200-1000)A
12V/24V
4~20mA
φ20
1
AHKC-EKB
0~(200-1000)A
±15V
5V
φ40
1
AHKC-EKBA
DC 0~(200-1000)A
12V/24V
4~20mA
φ40
1
AHKC-EKBDA
AC 0~(200-1000)A
12V/24V
4~20mA
φ40
1
AHKC-EKC
0~(500-1500)A
±15V
5V/4V
φ55
1
AHKC-EKCA
DC 0~(500-1500)A
12V/24V
4~20mA
φ55
1
WHKC-EKCDA
AC 0~(500-1500)A
12V/24V
4~20mA
φ55
1
AHKC-K
0~(400-2000)A
±15V
5V
64x16
1
AHKC-KAA
DC 0~(400-2000)A
12V/24V
4~20mA
64x16
1
AHKC-KDA
AC 0~(400-2000)A
12V/24V
4~20mA
64x16
1
AHKC-H
0~(500-3000)A
±15V
5V
82x32
1
AHKC-KA
0~(500-5000)A
±15V
5V
104x36
1
AHKC-HB
0~(2000-8000)A
±15V
5V
132x52
1
0~(10000-20000)A
±15V
5V
132x52
1
AHKC-HBAA
DC 0~(2000-8000)A
12V/24V
4~20mA
132x52
1
DC 0~(10000-20000)A
12V/24V
4~20mA
132x52
1
AHKC-HBDA
AC 0~(2000-8000)A
12V/24V
4~20mA
132x52
1
AC 0~(10000-20000)A
12V/24V
4~20mA
132x52
1
-
-
Download
-
[ | ] Manual of AHKC-EKB Hall Effect Transducer
pdf (276.06 KB) -
[ | ] CE Certificate of AHKC Series Hall Effect Transducer
pdf (106.02 KB) -
[ | ] IEC Certificate AHKC Series Hall Effect Transducer
pdf (419.93 KB) -
[ | ] LVD Certificate of AHKC Series Hall Effect Transducer
pdf (442.50 KB) -
[ | ] Catalogue of Acrel Hall Effect Transducer
pdf (2.24 MB)
-